IFP-2000
Scalable Analog/Addressable Fire Alarm Control
• 636 points per panel
• Networkable with up to 8 nodes (16 nodes for Select Distributors) for a total of 5088 points
• 2 SBUSs
• 8 Flexput® circuits that can be programmed as auxiliary power, notification appliance output, or as a conventional input.
• 9 amps of power
• Class A or B wiring for NACs, SBUS, and network.
• Compatible with either IDP (System Sensor) devices or SD (Hochiki) devices.
• Network dialing gives allows you to dial from one control panel on a network saving you money on telephone lines
• 4 x 40 LCD display
• Built-in synchronization for System Sensor®, AMSECO, Gentex®, or Wheelock®
|
|
 |
IFP-1000
Analog/Addressable Fire Alarm Control
• One onboard SLC circuit that can support 99 IDP (System Sensor) devices/99 IDP modules, or 127 SD (Hochiki) devices. Expandable to a total of 792 devices/792 modules IDP, or 1016 SD devices.
• 6 amps of power
• 6 Flexput circuits that can be programmed as auxiliary power, notification appliance output, or as a conventional input
• Built-in UL listed DACT (digital alarm communicator transmitter)
• 1 SBUS
• 4 X 20 LCD display
• Built-in synchronization for System Sensor®, AMSECO, Gentex®, or Wheelock®
|
 |
IFP-2000VIP
Scalable Analog/Addressable Fire Alarm Control w/Integrated Voice Evacuation
• All the features of the IFP-2000 fire alarm control panel
• Supports up to 64 speaker circuits that can be easily mapped with programming software.
• Uses distributed amplifier that can provide up to 1000 watts of power using either the VIP-50 (50 watt amp, 8 max) or VIP-125 (125 watt amp, 8 max)
• 3 user recordable voice messages that can uploaded and used for other job sites |
|
 |
IFP-1000VIP
Analog/Addressable Fire Alarm Control w/Integrated Voice Evacuation
• All the features of the IFP-1000 fire alarm control panel
• Supports up to 64 speaker circuits that can be easily mapped with programming software.
• Uses distributed amplifier that can provide up to 1000 watts of power using either the VIP-50 (50 watt amp, 8 max) or VIP-125 (125 watt amp, 8 max)
• 3 user recordable voice messages that can uploaded and used for other job sites |
 |
IFP-100
Analog/Addressable Fire Alarm Control
• One onboard SLC circuit that can support 99 IDP (System Sensor) devices/99 IDP modules, or 127 SD (Hochiki) devices
• 6 amps of power
• 4 Notification circuits that can be programmed as either aux power or as a notification output
• Built-in UL listed DACT (digital alarm communicator transmitter)
• 1 SBUS
• 4 X 20 LCD display
• Built-in synchronization for System Sensor®, AMSECO, Gentex®, or Wheelock® |
|
 |
IFP-100VIP
Analog/Addressable Fire Alarm Control w/Integrated Voice Evacuation
• All the features of the IFP-100 fire alarm control panel
• Supports up to 64 speaker circuits that can be easily mapped with programming software.
• Uses distributed amplifier that can provide up to 1000 watts of power using either the VIP-50 (50 watt amp, 8 max) or VIP-125 (125 watt amp, 8 max)
• 3 user recordable voice messages that can uploaded and used for other job sites
• Built-in synchronization for System Sensor®, AMSECO, Gentex®, or Wheelock®
|
 |
IFP-50
Analog/Addressable Fire Alarm Control
• One onboard SLC circuit that can support 50 IDP (System Sensor) devices/50 IDP modules, or 50 SD (Hochiki) devices
• 6 amps of power
• 4 Notification circuits that can be programmed as either aux power or as a notification output
• Built-in UL listed DACT (digital alarm communicator transmitter)
• 1 SBUS
• 4 X 20 LCD display
• Built-in synchronization for System Sensor®, AMSECO, Gentex®, or Wheelock®
|
|
 |
IFP-25
Hybrid Conventional-Addressable Fire Alarm Control
• Combines the convenience of conventional control panel programming and configuration using addressable devices that provide all the data required for calibrated smoke test as required by NFPA 72
• Built-in support for a combination of up to 25 Honeywell Fire System detectors and modules
• Programming is easily done just by setting the code wheels on the detectors or devices then the control panel automatically maps them to the correct zone.
• Custom programming can be done with a laptop by simple plugging into the control panel and opening your web browser, the control panel has a built-in web page dedicated to system programming.
• Built-in synchronization for System Sensor®, AMSECO, Gentex®, or Wheelock® |